FEATURES
- Designed to Meet Class 2, Div 2 Protection
- Purge/Pressure System
- NEMA 4X (IP66) sealed enclosure
- Water proof and dust proof
- Stainless steel construction
- Mid-size footprint
- Flexible mounting options
- Direct or KVM cabling to
host
CONTACT
HEADQUARTERS
11529 Sun Belt Ct.
Baton Rouge, Louisiana 70809
Phone
800.223.8050
International 001.225.298.0300
Fax
225.297.2440
E-mail
sales@vartechsystems.com
Website
www.vartechsystems.com
_____________________

Material Specifications
Regulator Body
Zinc w/ Enamel Finish
Regulator Handle & Bowl
Polycarbonate
Rapid Exchange Gauge
ABS Plastic
Tube Fittings & Valves
316 SS Forged Body
Tubing
316 SS 1/4” .035 Welded
System Nameplates
Silk screened Lexan® & SS
Fastener Hardware
Zinc Plated and Stainless
Steel
Mounting Plate
316 14 Ga #3 Brush SS
EXP Pressure Switch Body
Anodized Cast Alum.
Enclosure Warning
Nameplate
Silkscreened SS
The VT702ES is a NEMA 4X (IP66) LCD designed to meet Class 2, Div 2 protection.
The purge system uses a pressure switch to automatically trigger alarms in case
of pressure loss.
Slim and Economical
With its moderate weight and small footprint, the VT702ES is ideal for
applications where both space and budget are limited.
Durable
The VT702ES is fully enclosed in a sealed, NEMA 4X (IP66), easy-open, stainless steel case. The chassis has no external vents, so nothing can get under its skin,
including weather, dust, dirt, moisture, oil, chemicals or other harsh
contaminants. A hard-anodized aluminum heat exchanger and internal heat
management system keep it cool in environments where ambient temperatures
approach 50°C/122°F -- without using outside air. With its lightweight yet rugged construction, and either pre-cabled or bulkhead connectors, the VT702ES is easily mounted on walls, stands, arms or other industrial equipment. With optional brackets, it conforms to VESA flat panel mounting standards.
![]()
Display
19 Inch TFT, LCD screen shielded by a
Tempered Glass Protective Overlay
Resolution Capabilities
SXGA
Pixel Format
1280 x 1024*
Standard Connection
VGA, Serial, Power
Enclosure
316 Stainless Steel Sealed Anodized Aluminum Heat Sink
12" Handles
Environmental/Thermal
NEMA 4X (IP66)
Water Proof
Dust Proof
50ºC/122ºF
IP65
![]()
Purge System Mounting to Side (L/R), Top or Bottom
_____________________________________________________________
Z Type Purge System w/ Pressure Switch (Class 2, Div 2 Protection)
This Rapid Exchange® enclosure pressurization that operates on a supply of
compressed instrument air or inert gas. It regulates and monitors pressure within
sealed (protected) enclosure(s), in order to prevent combustible dust
accumulation or remove and prevent flammable gas or vapor accumulations. In
Class II areas, the system maintains a "safe" (1.0") pressure. This process
reduces the hazardous (classified) area rating within the enclosure(s), in
accordance with the NEC - NFPA 70, Article 500, NFPA 496 and ISA 12.4.
![]()
Shipping Weight
10 lb
Operating Temp. Range
40F to 120F
Supply Pressure Range
5 - 120 psi
Supply requirements
Clean air or inert gas
Safe Pressure Setpoint
.25"/1" @ safe pressure
Safe Pressure Flow Rate
0.1 - 3.5 SCFH - Enclosure integrity determines actual flow rate
System Supply Port
1/4" FPT
Enclosure Supply Fitting
1/4" tube fitting
Enclosure Reference Fitting
1/4" tube fitting
EPCU Conduit Port Size
1/2" FPT
EPCU Power Requirements
120 VAC 15amps
Dimensions
12" (H) x 8" (W) x 7.25" (D)
Height & Width dimensions reflect mounting plate measurements. Depth
dimensions reflects overall measurement of system, including components.
Mounting
Side (L/R), Top or Bottom
OPERATION
In accordance with system instructions, start-up requires air supply to be engaged
and enclosure power to be de-energized. In Class II areas, all dust must be
removed from the enclosure(s). The enclosure protection vent (if used) must be
tested and enclosure(s) must be sealed. The enclosure pressure control regulator is then used to set a safe reading on the enclosure pressure gauge. In Class II areas, power can be energized when safe pressure is stable. Loss of safe pressure in Class I or II areas requires immediate attention, unless power is de-energized. WPS style systems include an explosion proof differential pressure switch with form "C" contacts for audible or visual alarm systems.